Operations and maintenance
Operating and maintaining a data centre: routines, spares, procedures and records.
On this page
One register from design to operations
Most facilities are handed over with drawings, a 3D model, a control-system point list and a maintenance system that each name the same pump differently. Operations then spends its first year reconciling them. The reference approach gives every asset one key at design and carries it everywhere.
Design position. The register key is a design deliverable, like the single-line diagram. It goes on the drawing, the equipment label, the control-system tag and the maintenance record, and the handover is checked against it.
A maintenance programme built from failure modes
The programme starts from how each class of equipment fails, how that failure shows itself beforehand, and how long the warning lasts. Tasks and inspection intervals follow from that, not from a generic calendar. The method follows IEC 60812 for failure modes, ISO 14224 for the equipment taxonomy, and ISO 17359 and ISO 13374 for condition monitoring.
| Equipment | What to watch | How |
|---|---|---|
| Circulation pumps on drives | Seal leaks, bearing wear, cavitation, standby that will not start | Vibration against ISO 20816 zones (formerly ISO 10816), thermography, scheduled duty and standby swaps |
| Plate heat exchangers | Fouling, gasket leaks, cross-contamination | Approach temperature and pressure-drop trends, samples from both circuits |
| Strainers and raw-water screens | Blocking | Differential-pressure trend, back-flush count |
| CDUs and the technology loop | Filter loading, coolant chemistry, leaks | CDU flow and pump alarms, laboratory analysis of the coolant, leak detection |
| Water treatment | Corrosion, microbial growth | Laboratory analysis (pH, conductivity, inhibitor, metals, microbiology), corrosion coupons |
| UPS and batteries | Weak cells, hot connections, transfer faults | Ohmic trending, capacity test on a load bank, thermography, transfer tests |
| Busway and tap-off boxes | Loose or hot joints | Thermography (ISO 18434-1), contact-resistance measurement |
| Variable-speed drives | Fan and capacitor ageing, hot connections | Fault log, heat-sink temperature trend, thermography |
| Valves, check valves, air vents | Hidden failures: a valve that will not close, a check valve that passes | Planned exercise and closure tests, reverse-rotation check at pump changeover |
The maintenance standards named above (IEC 60812, ISO 14224, ISO 17359, ISO 13374, ISO 20816 and ISO 18434-1) are named for orientation. The research behind this site did not review them.
NFPA 70B, the electrical maintenance document many teams follow, became a standard in its 2023 edition, the edition the sources here describe; check which edition applies to your project. Trade sources point out that it becomes enforceable when an authority or a contract adopts it.12 On the management side, the part of ISO/IEC 22237 that covers operational information was, at the time of writing, still a technical specification rather than a full international standard.3
Design for the people who run it
Uptime Institute's 2025 outage analysis found that nearly 40 % of organisations had suffered a major outage caused by human error over the previous three years, and that the share of human-error outages caused by failure to follow procedures rose by ten percentage points.4 Uptime says the rise may be a consequence of rapid growth and staff shortages, without putting a number on it.4
Design can lower that risk: labels that match the procedures, isolation points that are easy to find and lock, procedures linked to the asset in the 3D model, and alarms that name the first action.
Commissioning and handover
The five commissioning levels run from factory acceptance through installation checks and start-up to functional performance tests and the integrated systems test, which runs the plant at design load on load banks and drops the utility supply.5 The reference handover adds one more check: every asset in the register is found on site, labelled, in the control system and in the maintenance system, before operations sign.
Sources
- NFPA 70B changing from guideline to standard. HFM Magazine, 2022-12-16. Read 2026-10-18.https://www.hfmmagazine.com/articles/4635-nfpa-70b-changes-from-a-guideline-to-a-standard
- NFPA 70B Compliance: What Changed and When It Actually Applies. Reliable Media (Reliamag). Read 2026-10-18.https://reliamag.com/guides/nfpa-70b-compliance/
- ISO/IEC 22237 & EN 50600: Data Centre Design Standard. GreenCalculus, 2026-06-19. Read 2026-10-18.https://www.greencalculus.com/standards/iso-iec-22237-en-50600-data-centre-design/
- Uptime Announces Annual Outage Analysis Report 2025. Uptime Institute, 2025-05-06. Read 2026-10-18.https://uptimeinstitute.com/about-ui/press-releases/uptime-announces-annual-outage-analysis-report-2025
- Data center commissioning levels and process field guide. Anvilfield, 2026-06-27. Read 2026-10-18.https://anvilfield.com/field-guides/datacenter/data-center-commissioning-levels-process/